Z-4RTD2

The Z-4RTD-2 module acquires up to 4 RTD signals (through 4 inputs regardless and isolated with each other) it converts them it to a temperature or resistance measure.

  • It’s possible to choose if the input is RTD-type: PT100, NI100, PT500, PT1000
  • It’s possible to choose the RTD-measure type: temperature (°C) or resistance(for each input)
  • It’s possible to choose if RTD-wire connection: 2-wire, 3-wire or 4-wire (for each input)
  • Wire measure and wire resistance compensation (if 3-wire connection)

  • Configuration of a filter applied to each input signal
  • It is possible to configure the module (node) address and baud-rate by Dip-Switches
  • It is possible to add/remove the module to/from RS485-bus without disconnecting the  communication or power supply.
  • It is possible to switch automatically RS485 to RS232 or vice versa

  • Resolution : 13bit (if filter=0-1); 14 bit (if filter=2-7)
  • Rejection : 50Hz or 60 Hz
  • Filter : (0-7) IIR and FIR; configurable between: 0 (deactivated), from 1(min) to7(max)
  • Accuracy : Initial: 0.05% of 350

See Related Products

Remote Control Unit with built-in IO and 3G+ modem S6001-RTU

Remote Control Unit with built-in IO and 3G+ modem S6001-RTU

Frequency Converter S111

Frequency Converter S111

Triple alarm threshold for control of analogue signals S113T

Triple alarm threshold for control of analogue signals S113T

Programmable Universal Converter with Bipolar output Z109REG-BP

Programmable Universal Converter with Bipolar output Z109REG-BP